Mô tả
| Operating voltage | 100 Vac to 440 Vac |
| Voltage measurement | 100 Vac to 440 Vac |
| Consumption | 15 VA max |
| Voltage tolerance | ±10% on indicated operating voltages |
| Measurement category (according to IEC 61010-1) |
CAT III |
| Accuracy | 1% full scale |
| Frequency range | 50 or 60 Hz +/- 5% (automatic adjustment to network frequency) |
| Current input | 5 A or 1 A (RMS) (class 1 C.T.) |
| Current input impedance | <0.1 Ohm |
| Number of outputs | RVC-3: 3 outputs RVC-6: 6 outputs RVC-8: 8 outputs RVC-10: 10 outputs RVC-12: 12 outputs |
| Output contact rating | Max. continuous current: 1.5 A Max. peak current: 5 A Max. voltage: 440 Vac |
| Alarm contact rating (voltage free contact) |
NO contact Max. continuous current: 5 A Rated/ max. breaking voltage: 250 Vac/ 440 Vac |
| Power factor setting | From 0.7 inductive to 0.7 capacitive |
| Starting current setting (C/ k) | 0.01 to 5 A |
| Switching time between steps | Programmable from 1 s to 999 s |
| Mode of switching | The modes of switching for all the programmable switching sequences are integral, direct, linear or circular |
| Power outage release | Quick automatic disconnection in less than 20 ms (50 Hz) in case of power outage or voltage drop |