Bảng Tra Lỗi Biến Tần Inverter Error ENC EN500 EN600

Failure code Failure type Possible reason Countermeasure
E-01 Overcurrent
during accelerating
process
Accelerating time is too short Prolong accelerating time
Improper V/F curve Adjust V/F curve setting,adjust manual torque boost or change to automatic torque boost
Restart rotating motor Set speed checking restart function
Low power source voltage Check input power supply
Too small power of the inverter Choose inverter with high-power
Output phase lose under vector control Check whether the motor wiring is in good condition
E-02 Overcurrent
during
decelerating
process
Decelerating time is too short Prolong decelerating time
Have potential energy load or big Inertia load Increase braking power of external energy consumption braking subassembly
Power of inverter is a bit small Choose inverter with high-power
E-03 Overcurrent
during constant
speed process
Load change suddenly or have
unwonted phenomena
Check or reduce break of the load
Acc./Dec. time is set to too short Prolong accelerating /decelerating time properly
Low power source voltage Check input power supply
Power of inverter is a bit
small
Choose inverter with high-power
E-04 Overvoltage Unwonted input voltage Check input power supply
Acc. time is set to too short Prolong accelerating time properly
Restart rotating motor Set speed checking restart function
E-05 Overvoltage
during
decelerating
process
Decelerating time is too short Prolong decelerating time
Have potential energy load or
big inertia load
Increase braking power of external energy consumption braking subassembly
E-06 Overvoltage
during constant
speed process
Unwonted input voltage Check input power supply
Acc/Dec time is set to too short Prolong accelerating decelerating time properly
Input voltage change abnormally Assemble reactor
Load inertia is a bit big Use energy consumption subassembly
E-07 Inverter control
power supply
overvoltage
Unwonted input voltage Check input power supply or look for service
E-08 Low-voltage
when running
Input voltage is too low Check the input voltage
E-09 Inverter overload
protection
Acc time is set to too short Prolong accelerating time
DC injection braking is too big Reduce DC injection braking current,prolong braking time
Improper V/F curve Adjust V/F curve and torque boost
Restart rotating motor Set speed checking restart function
Power source voltage is too low Check power source voltage
Load is too big Choose inverter with high-power
E-10
(A-10)
Motor overload
protection
Motor overload protection Adjust V/F curve and torque boost
Power source voltage is too low Check power source voltage
General motor run at low speed with big load Can choose frequency conversion motor for long time low speed run
Motor overload protection factor set incorrectly to set motor overload protection factor correctly
Motor blocked up or load change too suddenly and quickly Check the load
E-11
(A-11)
Motor underload
protection
The operating current of inverter less than underload threshold Confirm whether the parameters F19.08, F19.09 setting are reasonable
load divorced from motor Checking whether the load divorced from motor
E-12 The input phase
lose
The three-phase input power
supply is abnormal
Check the three-phase input power line is off or poor contact
Power supply board anomaly Look for service from manufacturer or agent
The control board anomaly Look for service from manufacturer or agent
E-13 The output
phase lose
When the motor runs inverter
three-phase output
unbalanced
Check whether the motor
three-phase winding is balance
When the motor runs inverter
three-phase output
unbalanced
Check whether the motor
three-phase winding is balance
Power supply board anomaly Look for service from manufacturer or agent
The control board anomaly Look for service from manufacturer or agent
E-14 Inverting module
protection
Transient overcurrent of the
inverter
Refer to countermeasure for
overcurrent
phase to phase short circuit or earthing short circuit of output
3 phase
wiring again
Air-path blocked or fan damaged To clear air-path or replace the fan
Ambient temperature is too high Lower ambient temperature
Connecting wire or insert on control board loose Check and connect the wire again
Unwonted current wave caused by missing output
phase etc.
Check wiring
Assistant power supply damaged and drive voltage lacking Look for service from manufacturer or agent
Unwonted control board Look for service from manufacturer or agent
E-15 Short circuit to
ground when
operation
Motor short circuit to ground The replacement of cable or motor
Hall component is damaged
or the hall wiring is poor or
the current detection circuit
is abnormal
Look for service from manufacturer or agent
E-16 Short circuit to ground
when power on
Motor short circuit to ground The replacement of cable or motor
The power supplier of the
inverter and the motor wiring
are reversed
Change the cable or the motor
Hall component is damaged
or the hall wiring is poor
Look for service from manufacturer or agent
E-17
(A-17)
Inverter overheat Continuous alarm on A-17
for more than 30 minutes
Cleaning or to improve the ventilation duct
Duct blockage Cleaning or to improve the ventilation duct
The ambient temperature is
too high
To improve the ventilation conditions, decreasing the carrier frequency
Fan damage Change new one
External fault emergency stop terminal closed Open external failure terminal after external failure is settled
E-18
(A-18)
External device
failure
Sudden stop terminal for external failure closed Open external failure terminal after external failure is settled
E-19 Current detecting
circuit failure
Connecting wire or insert on control board loose Check and connect the wire again
Assistant power supply damaged Look for service from manufacturer or agent
Hall component damaged Look for service from manufacturer or agent
Unwonted amplifying circuit Look for service from manufacturer or agent
E-20 External
interference
failure
The interruption protection is
triggered, but none of the actual overcurrent, overvoltage and short circuit signals have been detected
Press “STOP/RESET” button to reset or add external power supply filter from power input side
E-21 Internal
interference
failure
Internal disturbance serious Power off and restart, if the failure persists, seek the manufacturer or dealer service
E-22
(A-22)
PID reference
loss
PID given loss threshold setting is not reasonable To reset the relevant parameters
External given disconnection Check external given wiring
The control board anomaly Look for service from manufacturer or agent
E-23
(A-23)
PID feedback loss PID feedback loss threshold
setting is not reasonable
To reset the relevant parameters
Feedback signal
disconnection
Check external feedback signal
wiring
The control board anomaly Look for service from manufacturer or agent
E-24
(A-24)
PID error amount abnormal PID error abnormal detection
threshold setting is not
reasonable
To reset the relevant parameters
The control board anomaly Look for service from manufacturer or agent
E-25 Start terminal
protection
Terminal command effective
when power on
Check the external input terminal
state
E-26
(A-26)
Communication
failure
Baud rate set improperly set Baud rate properly
Serial port communication error Press “STOP/RESET” key to reset, look for service
Failure warning parameter set improperly Modify F05.04, F05.05
Upper device doesn’t work Check if upper device work and
wiring is correct
E-27 Reserved
E-28 Reserved
E-29 Reserved
E-30
(A-30)
E2PROM read
and write
wrongly
Mistake take place when read
or write control parameter
Reset by pressing “STOP/RESET” Look for service from manufacturer or agent
E-31 Temperature
detecting
disconnection
Temperature sensor fault Look for service from manufacturer or agent
The temperature detection circuit anomaly Look for service from manufacturer or agent
E-32 Self tuning failure Parameter setting not according to the motor nameplate Set parameter correctly according to the motor nameplate
Current anomaly when tuning Select inverter match the motor
Motor wiring error Check the motor three-phase wiring
E-33
(A-33)
Contactor
anomaly
Power board anomaly Look for service from manufacturer or agent
Contactor anomaly Replace contactor
E-34 The fault 1 Debugging use in factory
E-35 The fault 2 Debugging use in factory
E-36
(A-36)
The bus
capacitor
overheating
Poor cooling environment Improve the inverter heat dissipation environment
The inverter capacity is too small Select inverter match motor
Bus capacitance cooling fan is damaged Replace the bus capacitor cooling fan
E-37 Encoder
disconnection
Damaged encoder or poor wiring Check the wiring or the encoder
E-38 Overspeed
protection
Short acceleration time Prolong the acceleration time
Low inverter power Select high-power inverter
E-39 Large speed
deviation
protection
Short Acceleration/ deceleration time Prolong the acceleration time
Low inverter power Select high-power inverter
E-40 ~
E-50
Reserved
A-51 The main and
auxiliary
given frequency
channel
exclusiveness
alarm
Parameter setting error F01.00 and F01.03 cannot be set to the same channel (9: terminal encoder given except)
A-52 Terminal
function
exclusiveness
alarm
Terminal function parameters
setting repeatedly
Check the terminal function settings